voice air shower wire diagram (standard control)

Accessories Wiring Line Instructions

22

I. Overview

Air shower automatic control system is mainly used for automatic control of air shower, cargo shower and air shower channel. Can

Automatically realize the interlocking and unlocking of inner and outer doors; start and stop of lighting; automatic induction of human body and start and stop of fans

Start and stop functions. The product has relevant voice prompts during the automatic process, and has air shower time, before and after

Flexible functions such as door unlock delay time and lighting delay time adjustable.

2. Schematic diagram of the mask on the main board and the description of the buttons

23

Schematic diagram of LCD air shower panel

24

Schematic diagram of digital tube air shower panel

A. Description of keys on the air shower control panel:

1. Emergency stop button: Press the emergency stop button at any time, the red emergency stop indicator light will be on, and it will be automatically disconnected

All outputs except lighting, when pressed again, the system returns to the initial state. This button is mainly used for internal

When the outer door cannot be unlocked, the air shower cannot be closed automatically, or other maintenance is required.

2. Air shower button: After the inner and outer doors are closed, press the manual button, and the system will switch to the air shower process. this

The button is mainly used when the door magnetism, infrared failure or fan maintenance and overhaul.

3. Lighting button: Use the ”lighting” button to switch on and off the indoor lighting of the air shower. This button is mainly used

When the door sensor fails or the lamp is overhauled.

4. Up and down buttons: before or after the air shower starts, use the up and down buttons to adjust the air shower delay

Time; make adjustments or options when entering internal parameter settings.

B. Conventional air shower workflow:

1. Entering the clean area:

1.1 When the person entering the clean area opens the outer door, the voice prompts: “Hello, please stand in the sensing area”

The electric lock of the inner door is automatically locked to prevent the unpurified air in the air shower room from flowing into the clean area, and the lighting of the air shower room On, the outside work indicator light is on.

1.2 After entering the air shower, the infrared sensor of the system starts to detect whether there is anyone, if someone is detected, the system will Promptly transfer to the air shower process.

1.3 Lock the inner and outer doors before the air shower, start the fan to start the air shower, and at the same time, the air shower countdown starts timing. Voice prompt: “Working, please turn your body 360 degrees”.

1.4 If the system cannot detect anyone in the air shower room within the specified time after the outer door is closed, it will return to the standby state.

1.5 During the air shower, if someone presses the emergency stop switch, the air shower will end. Press the emergency stop button again to cancel the emergency stop state.

1.6 After the air shower is over, the inner door is unlocked, and the voice prompts: “The air shower is complete, please exit through the back door”.

1.7 After the person walks out of the air shower and closes the inner door, the system returns to the initial state and waits for the next use.

1.9 After the air shower is completed, the inner door is unlocked. The personnel inside did not leave the air shower within the specified time

room, the system defaults that the person may have left, and automatically returns to the standby state.

1.10 After the lighting is on, if it is not triggered again within the specified time, it will automatically turn off.

2. Leaving the clean area:

2.1 Open the inner door, the electric lock of the outer door is self-locking, the lighting of the air shower room is on, and the working indicator light is on;

2.2 People walk into the air shower room, close the inner door, and the system starts to detect whether there is anyone in the air shower room, if

If no one is detected within the specified time, the inner and outer doors will be unlocked;

2.3 If someone is detected, the system will lock the inner door when the person opens the outer door, and lock the inner door when the outer door is closed.

After that, the system returns to the initial state;

2.4 In case of special circumstances, personnel can choose to return to the clean area, the system waits for the personnel to open the inner door,

The outer door is powered on and self-locked. When the inner door is closed, the system returns to the initial state;

2.5 After the outer door is opened, if no one is detected within the specified time, if the outer door is opened first at this time, the system will

The system transfers to the process of entering the clean area; if the inner door is opened first at this time, the system transfers to leaving the clean area process.

2.6 After the lighting is on, if it is not triggered again within the set time, it will automatically turn off.

C. Air shower indicator light and digital tube display instructions:

1. Air shower countdown: double-digit red digital tube or LCD display, used to display the air shower time during work

The setting value and the remaining time of the air shower are used to display the menu parameters when setting the menu;

4. Air shower light: When this light is on, it indicates that the air shower fan has been started automatically or manually;

5. Emergency stop light: When this light is on, it indicates that the system is in emergency stop state.

6. Illuminating light: When the illuminating light is turned on, the light is on, and it can be turned off or started according to the key.

3. Schematic diagram of sub-board wiring Input and output terminal interface description:

25

1. Strong current input interface

a. Power supply: 110-230VAC (the silk screen mark is 220V AC IN)

2. Strong current output interface

a. Fan: 1A 220VAC (connected to the AC contactor coil, the silk screen mark is the fan relay)

b. Lighting: 1A 220VAC (If there are many lamp tubes, you can connect the intermediate relay, and the silk screen mark is the lighting indicator light)

c. Working instruction: 1A 220VAC (the silk screen mark is the working indicator light)

d. Power indicator: 1A 220VAC (the silk screen mark is the power indicator light)

3. Weak current input interface

a. Inner door magnetic switch: passive contact (marked by silk screen as inner door magnetic)

b. External door magnetic switch: passive contact (marked by silk screen as external door magnetic)

c. Infrared sensor switch: passive contact (marked by silk screen as infrared)

4. Weak current output interface

a. Infrared switching power supply: 12VDC (marked as 12V GO on silk screen)

b. External door electric lock: 600mA DC12V (the silk screen mark is the external door electric lock)

c. Inner door electric lock: 600mA DC12V (inner door electric lock with silk screen mark)

4. Operating Instructions

Air shower working parameter setting:

1. Air shower time setting: before or after the air shower starts, directly press the up and down adjustment buttons

The air shower delay time can be changed, the adjustment range is 2-60 or 2-99 seconds, and it is controlled by a double-digit digital tube or LCD

display, the system automatically saves the parameter value 5 seconds after the adjustment is completed.

2. Delay setting for unlocking the outer door after wind shower (TI): press the emergency stop button continuously for 30 seconds, the system enters the internal parameter

Number setting, the digital tube display: TI, and then press the up or down button to check the unlocking delay of the outer door after the air shower

Time, the unit is second, press the up or down key to adjust within 0-60 seconds, air shower key to confirm

And enter the next option, there is no key within five seconds to trigger the system to save the parameters and exit the setting;

3. Delay setting for unlocking the inner door after the air shower (TO): After completing the setting of the outer door, press the air shower button again within five seconds,

Enter the delay setting (TO) of unlocking the inner door after the air shower, and you can check it through the up and down adjustment keys and adjust it between 0-60

Adjust time in seconds. Press the air shower button to confirm and enter the next option, if there is no button to trigger the system within five seconds

Save the parameters and exit the settings;

4. Internal and external door interlock door opening delay setting (TC): After completing the internal door setting, press the air shower button again within five seconds,

Enter the interlock door opening delay setting (TC) of the inner and outer doors, which can be viewed and adjusted between 0-60 by pressing the up and down adjustment keys.

Adjust the door opening delay time of the inner and outer door interlocks within seconds. Press the air shower button to confirm and enter the next option, five seconds

There is no key to trigger the system to save the parameters and exit the setting;

5. Lighting delay setting (TL): After completing the interlock setting of the inner and outer doors, press the air shower button again within five seconds,

Enter the lighting delay setting (TL), through the up and down adjustment keys to view and adjust within 0-60 minutes

Save the lighting delay off time. Press the air shower button to confirm and enter the next option, if no button is touched within five seconds

Send the system to save the parameters and exit the setting;

6. Program selection setting (TD): After completing the lighting setting, press the air shower button again within five seconds to enter the program

Program selection setting (TD), through the up and down adjustment keys to view and select the program in 00-02. 00:

Normal air shower program, 01: with door but no induction program, 02: with induction without door program. Press the air shower button to confirm and

Enter the next option, there is no key within five seconds to trigger the system to save the parameters and exit the setting;

7. Inner and outer door exchange setting (TN): After completing the program selection setting, press the air shower button again within five seconds to enter

Enter the exchange setting of the inner and outer doors (TN), and use the up and down adjustment keys to view and select the program in 00-01

sequence. 00: normal, 01: interchangeable. Press the air shower button to confirm and enter the next option, if no button is pressed within five seconds

Send the system to save the parameters and exit the setting;

5. Precautions for use:

1. Product opening size: L×W=245×125 (MM)

2. Due to the limitation of the circuit board, it is recommended not to connect external devices greater than 100W to each interface terminal.

Larger power or more lamp panels can be switched through AC contactors and intermediate relays;

3. When installing a human body infrared switch, it should be installed in the middle of the air shower room, and it should be installed when the air shower room is long.

2 human body infrared switches (used in parallel), when installing 2 human body infrared switches, the front door and

Install one at each position near the inner door;